|
|
Sign In | Register Now Why Register? |
||
|
|
|||
|
|
|||
|
IAEI News>Issue Listing>March/April 2003 >The Truth About AFCIs (Part 2)
Photo 1. Branch/circuit-breaker type AFCI This is the second of a two-part article on arc-fault circuit interrupters (AFCIs). The first part was published in the January/February issue of this magazine and dealt with questions related to the technology and how it is addressed in the product standard. Part II focuses on application and installation in accordance with the National Electrical Code. AFCIs have just become required for installation in residences under the NEC. The intent of this article is to enlighten the reader on facts about AFCIs. Background Electricians, contractors and users should be aware that AFCIs are installed in locations that the standard circuit breakers are installed. They can be retrofitted into existing loadcenters and panelboards. Electrical connections are similar to those of a circuit breaker GFCI in that they have a load-neutral connector and a pigtail connection to the panel neutral bus. It should be very difficult to cause an unwanted tripping condition in a dwelling unit branch circuit. When tripping occurs, it is most likely a result of an arcing condition or an improperly wired circuit. The AFCI is designed to trip when certain conditions likely to cause a fire exist in the circuit. There has been relatively little experience in locating these conditions. This paper provides some guidelines that may be helpful. Part I of the article lists conditions under which the AFCI is designed to trip. The discussion focuses on the branch/feeder AFCI, which is the only commercially available AFCI. Applying AFCIs under NEC 210.12 As regards what must be protected, the requirement is clear as written: "All branch circuits that supply 125-volt, single-phase, 15- and 20-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter listed to provide protection of the entire branch circuit."1 This includes outlets for receptacles, for lights, for fans, and so forth in circuits that supply bedrooms. Retrofit applications in 2-wire
circuits Required locations under the NEC Hotels and dormitories Smoke detector circuits Bedroom closets Commercial applications Tripping Causes on Installation Because there were a significant number of reports of AFCIs tripping on installation, Square D re-contacted those who had reported the tripping after the initial inquiry from them. The following is a list of the findings.
Crossed neutrals are defined here as neutrals from multiple circuits either crossed or touching. Shared neutrals are defined here as multi-circuit neutrals. Reported difficulties in troubleshooting installation problems are an indication of a learning curve and are not a reflection on poor performance of the AFCI. Today’s AFCIs are performing their detection function properly and are finding problems that should be corrected. There is some resistance to this change as is to be expected with any change. However, this small and informal survey indicates that installers are learning the issues that are uncovered by AFCIs and that they can be found and corrected. When the circuit is corrected, not only is the circuit correct, it also has additional AFCI protection operating to help retain it free of hazardous arcing. Shared neutrals Contractors and users should understand that thereare some drawbacks to using shared neutrals. For example, if a 2-pole, common-trip version is used, then both circuits are interrupted during a fault. If the 2-pole, common-trip version is used, then both circuits are interrupted during a fault. If the 2-pole circuit breaker has independent trip, then when a circuit is tripped and an outlet device is removed (assuming a dead circuit), if the home run is split at that point, the wiring in the box is not really dead. Another example of shared neutral wiring disadvantages is the result if the home run neutral is lost—a motor load will take one side of the circuit to zero, putting the loads on the other side to 240 volts. This tends to play havoc with many 120-volt devices. Further, cable manufacturers are apparently planning cables that contain four wires plus ground for exactly this kind of application. Test equipment
We will discuss each item briefly. Verification of the
installation
To perform this test, disconnect all loads and verify that unconnected wire ends are insulated. Disconnect the load wire to any AFCI or GFCI in the circuit because these devices may be damaged by high voltage. Use an insulation resistance tester that will apply a direct current voltage of at least 500 volts to the circuit under test. All resistance readings should be at least one megohm (1,000,000 ohms). A successful test will indicate that the insulation is intact and initiation of an arc would be highly unlikely for the portion of the circuit tested. Recognize that neither of these tests will identify loose connections. Good workmanship is required as always. Verification of the AFCI The authors are not aware of commercially available testers other than those mentioned below that trip the AFCI by applying a ground fault. Tripping the AFCI from a load Finding the cause of AFCI
tripping The AFCI function will be sensing an arc that occurs because insulation or isolation is not adequate. The problem or fault may be in one or a combination of these three conditions:
Here are some steps that may be
useful: b) The most likely cause of tripping in a new installation is wiring. Check for neutral (grounded circuit) conductors that are shared or crossed with those of other circuits, or neutral conductors that are grounded on the load side of the AFCI. c) Unplug all appliance and extension cords connected in the circuit. If tripping continues to occur when the AFCI is turned on, the fault is in the fixed wiring system. d) Similarly, turn off all fixed appliances such as lights and ceiling fans that have switches. Since these circuits cannot be fully disconnected (line, neutral and ground), tripping occurrences with their switches turned off does not necessarily mean that they are fault free. e) If the AFCI does not trip when all plugs are disconnected, turn on the AFCI again and reconnect the plugs one by one. Then turn on fixed lights and appliances. This procedure may locate the faulted cord or appliance. f) Because arcs are sometimes sporadic, turning off the circuit may temporarily clear the arc and it may not immediately reappear when the circuit is re-energized. For this reason, the arc may not be located by unplugging and reconnecting appliances. If the arc has been located to be in the fixed wiring system, or if the arc has not been located by removing plug-in loads, some of the following techniques may be helpful.
Note: De-energize the load center by turning off the main disconnect, if possible, before conducting the following checks. By means of a reliable voltmeter, verify that voltage is not present. g) Apply the insulation resistance test described in a response to a question above to check for insulation adequacy line-to-neutral, line-to-ground and neutral-to-ground. Alternatively, use an ohmmeter to check for electrical continuity line-to-neutral, line-to-ground and neutral-to-ground. Continuity indicates presence of a fault. The insulation resistance check is the preferred method. h) Indication of adequate insulation in a circuit that has been identified as having an arc fault may point to a series fault, that is a broken conductor or a loose connection. i) The line-to-ground sensing is for small leakage current of about 50 milliamperes (0.050 amperes) and above. It may not be visible as an arc. Any technique used to find a ground fault would be useful for locating an arc to ground. j) Once the fault is located, damage must be repaired or improperly operating equipment or appliances must be replaced. k) In most cases, the steps noted above will help locate the fault. It is important to recognize that the AFCI has provided an indication of a condition that could become a fire hazard. Do not continue to use the circuit without a correction. The introduction of AFCIs is a change. There is a learning curve for the entire industry. Through this change, it is clear that AFCIs are finding problems with installations, both in older upgrades and in new construction, in fixed wiring as well as in extensions to loads. The data indicates that there are many potential fire causes that the AFCI will help avoid becoming fires. When they are applied as intended, we will see results in more potential fire causes corrected. 1 Section 210.12(B), National Electrical Code 2002, (National Fire Protection Association, Quincy, MA), p. 70-54.
|
| |||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||