|
|
||
|
IAEI News>Focus on the Code >CMP-8
Question
1. NEC Section
370-28(a)(3) states that conduit bodies of smaller dimensions
than required in (a)(1) may be used for combinations of
conductors less than the values in table 1, chapter 9, up to
the maximum that is permanently marked in the conduit body.
The contractor intends to pull twelve No. 2/0 conductors
through a 3 in. C-condelet, which is stamped "maximum 3
No. 300 MCM XHHW conductors" instead of using properly
sized pull boxes. The conductors are oversized for de-rating
purposes. Does this violate Section 370-28? — I.N. Answer 1. Thank
you for your question regarding the application of
370-28(a)(3). Because you referenced 370-28(a) (3), I assume
you are using the 1999 edition, rather than the 2002, in which
Article 370 was relocated as Article 314. Additionally, I am
assuming the use of Type THHN insulation and a 3-inch EMT
raceway. Subsection 370-28(a) limits its application
to the minimum dimensions of pull or junction boxes installed
in a raceway or cable run where the conductors are No. 4 or
larger. Parts (1) and (2) deal with the dimensional
requirements when straight, angle and U pulls are made.
Subsection 370-28(a)(3) permits the use of boxes or conduit
bodies with dimensions less than those required in
370-28(a)(1) or (2) when the installation complies with the
stated conditions. The stated conditions are: 1. The combination of conductors being used
is less than the maximum conduit or tubing fill permitted by
Table 1 of chapter 9. 2. The box or conduit body has been
approved for and is permanently marked with the maximum number
and maximum size of conductors permitted. Table 5 of chapter 9 gives the approximate
area, in square inches, of the No. 2/0 AWG THHN insulated
conductors as 0.2223. There are twelve No. 2/0 AWG THHN
insulated conductors being installed. This results in a total
of 2.6676 square inches [12 x 0.2223 square inches = 2.6676].
Table 1 of chapter 9 requires a maximum 40 percent fill for
more than two conductors in a conduit or tubing. Table 4 of
chapter 9 gives the 40 percent fill for a 3-inch EMT as 3.538
square inches. The twelve No. 2/0 AWG Type THHN insulated
conductors require 2.6676 inches and the 3-inch EMT is
permitted to have a maximum of 3.538 square inches at 40
percent fill. This satisfies one of the two conditions stated
in 370-28(a)(3). The C-condelet is stamped with a maximum of
three No. 300 MCM XHHW insulated conductors. The use of the
term MCM is changed to kcmil in the 1999 NEC. Table 5
of chapter 9 gives the approximate area of the No. 300 kcmil
XHHW insulated conductors as 0.4536 square inches. The stamp
is for a maximum of three such conductors. This results in a
total square inch requirement of 1.3608 [3 x 0.4536 square
inches = 1.3608]. The twelve No. 2/0 AWG Type THHN insulated
conductors require a minimum of 2.6676 square inches, while
the condelet is suitable for no more than 1.3608 square
inches. Therefore, this proposed installation is not permitted
by the Code. — Wayne A. Lilly, CMP-08 | Return
to top | Question
2. I am a project inspector for a large
institutional project in the San Francisco Bay area of
California. The electrical contractor has supported his
conduits from the drywall utilizing drywall inserts and
one-hole straps. In the past, I have always required that the
conduits and boxes be supported from framing members (i.e.,
studs) and not from the drywall only. Can you help me with the
requirements on this issue? I have reviewed the Code and
it is vague about the adequate support of the conduit and
boxes. Thanks for any help you can give me to
convince the contractor to support from the metal framing
members and not just into the drywall. — M.W. Answer 2. Thank
you for your question regarding the supporting of conduit. I
hope my answer will be of help. You did not state which Code you are using. I will assume that the 2002 edition is
applicable in this situation. I will also assume that the
voltages involved are less than 600. Your question
specifically deals with supports. You did not mention which
conduit is being installed. As you are aware, there are
several conduits addressed by the NEC. Each conduit
article has requirements for supporting that are specific to
the conduit addressed by the article. When comparing those
requirements, we see there are some differences. During the last few cycles, the NEC has made an effort to clearly distinguish between securing and
supporting of raceways. The intention is to provide more
uniform language that is easier to understand and apply. An
example is section titles that have been changed from
"Supports" to "Securing and Supporting"
with separate requirements for "Supports" and
"Securely Fastening." Conduits are to be securely fastened so
that strain and stress will not be transmitted to their
termination points. For instance, 342.30 requires intermediate
metal conduit (IMC) to be "securely fastened within 900
mm (3 ft) of each outlet box, junction box, device box,
cabinet, conduit body, or other conduit termination. Fastening
shall be permitted to be increased to a distance of 1.5 m (5
ft) where structural members do not readily permit fastening
within 900 mm (3 ft). Where approved, conduit shall not be
required to be securely fastened within 900 mm (3 ft) of the
service head for above-the-roof termination of a mast." Supports are installed to aid in preventing
damage between points where the conduit is securely fastened,
such as might occur at a conduit coupling. Each conduit
article has requirements for supporting the conduit. For
instance, the support requirements for flexible metal conduit
(FMC), as found in 348.30, are "Horizontal runs of
flexible metal conduit FMC supported by openings through
framing members at intervals not greater than 1.4 m (4½ ft)
and securely fastened within 300 mm (12 in.) of termination
points shall be permitted." The NEC does not provide for the
methods that are to be used in meeting the requirements for
securely fastening and supporting conduits. Because of weight
differences, the methods for securely fastening and supporting
a run of metric designator 103 (trade size 4) rigid metal
conduit (RMC) are different than those for metric designator
12 (trade size 3/8) flexible metal conduit (FMC). Use of
wording such as "securely fastened" is meant to
convey that the conduit is to be fastened in such a manner
that the conduit will not move. This will prevent damage at
the conduit termination. Support requirements are meant to
permit some movement, but not movement that will damage the
conduit or conduit couplings. It is the responsibility of the
authority having jurisdiction (AHJ) to determine what methods
are best suited for the installation circumstance. The use of
one-hole versus two-hole straps and toggle bolts versus screws
directly into wood are decisions that the AHJ must make. There
may be additional requirements specific to local conditions
such as seismic considerations. Your question also mentioned boxes. Support
of boxes is covered in 314.23. This section does provide some
specific guidance relative to the support of boxes. The AHJ
must determine what methods are appropriate for the
installation circumstance. — Wayne A. Lilly, CMP-8 | Return
to top | Question
3. I have a question concerning the minimum and
maximum mounting height of a main breaker in a 125a, NEMA3
panel installed at a single family dwelling. The inspector
says that the Code states that the main breaker handle
must be between 5' 6"and 6' 6". Is this true? If so,
where is it stated in the Code? The only thing I have
found is in 230.70(a)(1), (2), (3) and 404.8(A), which states
6' 7" max to center of breaker or disconnect handle, but
nothing on minimum height requirements. The main breaker in
the panel is currently at 4' 6" and the meter can is at
6' to the center, mounted directly above the panel with an
offset nipple. — F.M. Answer 3. In
2002 NEC 230.70(A)(1), (2), and (3), and 404.8(A)
state, a maximum of 6' 7" to center of breaker or
disconnect handle. The only articles to mention a minimum
height are 550.11(A) and 551.77(D) for mobile homes and
recreational vehicles with a minimum of 24" above the
ground. On a single-family dwelling, I can find no requirement
to minimum height. — Joe Bolesina, CMP-9 | Return
to top | Question
4. This question concerns the use of expansion
joints as discussed in NEC 1999, Section 300-7(b). The
text states, "raceways shall be provided with expansion
joints where necessary to compensate for thermal expansion and
contraction." The FPN then discusses the 0.20
co-efficient for steel conduit, which could be applied based
on the values in Table 347-9(A) for rigid nonmetallic conduit. According to 347-9, Expansion Fittings,
under rigid nonmetallic conduit, provisions must be made for
thermal expansion and contraction when the conditions are such
that there could be a 1/4" movement. Does this
requirement for thermal expansion and contraction apply to
rigid metallic conduit? Are expansion fittings required for rigid
metallic conduit? For example, if 100 feet of rigid metallic
conduit is subject to 100ºF temperature change, then the pipe
would expand/contract 4.1" x 0.20 = 0.82". I don't see anything in the NEC that
addresses provisions for the expansion/contraction of rigid
metallic conduit, other than the FPN under 300-7(b). I realize
that the FPN is for clarification or explanation; but,
nonetheless, it seems that 1/4" movement is the same
regardless what the conduit material is. Provisions must be
made for rigid nonmetallic conduit when the movement is
1/4". Does this same requirement apply to other
conduits (specifically, RMC)? Section 300-7(b) seems to
require it. But I can't see anything in the Code that
spells it out as clearly as 347-9 does for rigid nonmetallic
conduit. What are the requirement, authority and
procedure for RMC?—K.C. Answer 4. Thank
you for your interesting questions regarding the use of
expansion joints in rigid metal conduit (RMC) and other
metallic conduits and tubing. You are correct in your assessment that a
1/4-inch or more movement of rigid nonmetallic conduit
requires the application of expansions fittings. There are
other specific requirements for expansion fittings. For
example, nonmetallic auxiliary gutters as required in
374-9(e)(2)(a)(4) and (b)(2). You are also correct that
300-7(b) of NEC 1999 requires the use of expansion
fittings for raceways where necessary to compensate for
expansion and contraction. This requirement applies to
metallic as well as nonmetallic raceways. FPNs are informational. They are not
enforceable. However, the FPN in 300-7(b) does provide
information on how to determine the expansion for RMC, IMC and
EMT. The illustration you gave is approximately correct. There
will be roughly an expansion of 0.82-inches per 100 feet for
the 100ºF temperature change in your example. However, there
are no provisions, as there are for RNC, for establishing an
entry threshold, such as 1/4-inch, at which expansion fittings
are required. The language in 300-7(b) requires the use
of expansion fittings "where necessary." A clear
need has been established for the use of expansion fittings
with RNC. Panel 8 has taken the necessary action by requiring
their use in 347-9. However, a need for expansion fittings has
not been demonstrated for RMC, IMC, or EMT. The Code does
not require the use of expansion fittings for RMC, IMC, or EMT.
If, in the future, a need for the fittings can be demonstrated
a Code proposal should be made to change the present
requirements.—Wayne A. Lilly, CMP-08 | Return
to top | Question
5. The following is a description of a situation
followed by a two-part question. A NEMA 3R enclosure is connected to a
NEMA 3R disconnect via a horizontal run of 2" EMT.
Fittings assumed to have the UL listed continuous ring in the
throat to meet UL requirement for raintight EMT fittings. The first question is whether or not
the EMT fittings should have a gasket at the enclosure and
disconnect in order to retain its raintight listing. The second question is if the EMT
fittings do not have a gasket at the entry to these
enclosures, does that affect the raintight listing of the
enclosures? I have been told that 3R will allow
the enclosure to leak as long as it does not create a short or
ground-fault condition. Thus, the lack of gaskets on the
EMT fittings. I think that the gaskets are required both
to retain the raintight features of the conduit fittings and
the enclosures. — R. D. Answer 5. Thank
you for your question regarding the use of electrical metallic
tubing (EMT) raintight type fittings and NEMA 3R equipment.
Your question did not specify which Code you are
working under. I will assume you are using the 2002 edition. I
will also assume that the NEMA 3R equipment is the correct
choice for the application and that the equipment is installed
in a wet location. The following is based on operational
voltages of less than 600 volts. We will begin by reviewing some of the more
pertinent information and Code requirements. Part 1 of
the UL Directory General Information for Electrical
Equipment, commonly referred to as the UL White Book,
under the heading "Enclosure Types" lists the
enclosure type numbers and the degree of protection provided
by each within specific environmental conditions. This
information states that a NEMA 3R enclosure type is suitable
for outdoor use and will be "undamaged by the formation
of ice on the enclosure." NEMA 3R equipment is not
suitable for use in areas where there is splashing or
hose-directed water. These applications would require a NEMA 4
enclosure. Additional information provided in the
White Book under the heading "Enclosure Types"
states "A Type 3R enclosure may be marked ‘Rainproof.’"
We are further told that a "Type 3 enclosure may be
marked ‘Raintight.’" Article 100 of the NEC defines rainproof as "constructed, protected, or
treated so as to prevent rain from interfering with the
successful operation of the apparatus under specified test
conditions." The word raintight is defined by
Article 100 as "constructed or protected so that exposure
to a beating rain will not result in the entrance of water
under specified test conditions." Although these are
subtle differences, it is important to use these terms
correctly. Your question did not specify if the
enclosure and disconnect fall within Article 312 or Article
314. Section 312.2(A) states, in part, "In damp or wet
locations, surface-type enclosures within the scope of this
article shall be placed or equipped so as to prevent moisture
or water from entering and accumulating within the cabinet or
cutout box and shall be mounted so there is at least 6 mm (1/4
in.) airspace between the enclosure and the wall or other
supporting surface. Enclosures installed in wet locations
shall be weatherproof." Section 314.15(A) states,
"In damp or wet locations, boxes, conduit bodies, and
fittings shall be placed or equipped so as to prevent moisture
from entering or accumulating within the box, conduit body, or
fitting. Boxes, conduit bodies, and fittings installed in wet
locations shall be listed for use in wet locations." Section 358.6 requires EMT, factory elbows,
and associated fittings to be listed. Section 358.42 states,
"Couplings and connectors used with EMT shall be made up
tight. Where buried in masonry or concrete, they shall be
concrete tight type. Where installed in wet locations, they
shall be of the raintight type." Section 110.3(B) states,
"Listed or labeled equipment shall be installed and used
in accordance with any instructions included in the listing or
labeling." In light of the foregoing information, I
will try to answer your questions. If the equipment is
installed in a wet location per 312.2(A) or 314.15(A), water
must not be permitted to enter the enclosure or box.
Therefore, fittings that are connected to the enclosure or box
must be installed so as to prevent the entrance of water.
Further, Sections 358.6 and 358.42 require the fitting to be
listed as raintight type. The use of sealing hubs and sealing
locknuts would be examples of installation methods that
prevent water entry. Sealing locknuts, as found under the
heading Conduit Fittings (DWTT) in the UL White Book,
"are intended for use with threaded rigid metal conduit
and intermediate metal conduit." The information found
under this heading also permits sealing locknuts for use with
listed wet location fittings "where so marked on the
fitting carton." If a sealing hub or fitting is used
gaskets, or O-rings, must be installed to maintain the
integrity of the box or enclosure against moisture entry. I
would agree that enclosures or boxes located in wet locations
that are installed so that water may enter are not
code-compliant. — Wayne A. Lilly, CMP-08 | Return
to top | Question
6. I am located at the U.S. Naval Base in Greece. A
U.S. contractor is installing 3/4" flex conduit
liquidtight in lengths greater than 6 ft for a branch circuit
from a power panel to a wiring cabinet utilized for electronic
communication devices. My understanding from the 1999 NEC is
that flex conduit in any form is not allowable in lengths
greater than 6 ft. The contractor states new code changes have
deleted this requirement. Is this true? Thanks for your help. — E.F. Answer 6. I
very much appreciate this opportunity to address your question
regarding the use of liquidtight flexible conduit. I hope my
response will be helpful. As I understand your question, my
answer will be based on the changes between the 1999 and 2002
NEC editions. The question did not specify the use of
liquidtight flexible nonmetallic conduit (LFNC) or the use of
liquidtight flexible metallic conduit (LFMC). I will answer
the question for both types of liquidtight flexible conduit. First we will take a look at LFNC. A
definition for LFNC can be found in 351-22 of the 1999 NEC and
in 356.2 in the 2002 NEC. Although there are some minor
changes in these sections, the definitions are the same for
both. Looking at these sections reveals that there are
actually three definitions, one for each type of LFNC. The
three types are LFNC-A, LFNC-B, and LFNC-C. The uses permitted and not permitted for LFNC
are found in 351-23 of 1999 NEC and 356.10 and 356.12 of 2002
NEC. Sections 351-23(b)(3) and 356.12(3) provide one of the
uses not permitted for LFNC. These sections stipulate that
LFNC lengths longer than 6-feet are not permitted to be used.
However, the language in both sections goes on to permit
longer lengths under certain circumstances. The first of these circumstances permits a
longer length if "a longer length is approved as
essential for a required degree of flexibility." This
requires the AHJ to determine if a length longer than 6 feet
is essential. If the AHJ determines that a longer length is
"essential for a required degree of flexibility" any
of the three types of LFNC may be used. The other circumstance
permits LFNC to be installed in any length if it is Type LFNC-B.
In either circumstance, the applicable installation
requirements of the Code must be met. The answer for LFNC is that there are no
differences in the length requirements between the 1999 and
2002 Codes. There was a change between the 1996 and 1999
editions, which permitted Type LFNC-B to be used in lengths
longer than 6 feet. Section 351-4 of 1999 NEC and Sections 350.10
and 350.12 of 2002 NEC provide the uses permitted and not
permitted for LFMC. LFMC is not restricted in length by either
Code in these sections. However, 250-118(6) and (7) in both
editions limit the length of LFMC where it is used as an
equipment grounding conductor. I hope I have addressed your question. If not,
please feel free to contact IAEI again. — Wayne A. Lilly,
CMP-8 | Return
to top | Question
7. Reviewing Article 318 on cable trays, I do not
find a provision that allows use of solid bottom cable tray
for single-conductor power cables. Specifically, 318-9 allows
the use of solid bottom tray for multiconductor control and/or
signal cables. However, I see no mention of solid bottom tray
in 318-10. Is solid bottom tray suitable for use with
single-conductor power cables less than 2000 V? If so, what
derating factors or ampacity tables are used? — J. A. Answer 7. Thank
you for your question regarding the use of single-conductor
cables with cable tray. You did not specify which Code you are using. However, you did refer to Article 318. The
article on cable tray was relocated from 318 to 392 in the
2002 edition. For that reason, I will assume you are using NEC-1999. Because your question deals with
single-conductor power cables, I will assume you are
installing the cables in an industrial establishment as
required and permitted in 318-3(b). Section 318-3(b) states,
in part, "The wiring methods in Section 318-3(a) shall be
permitted to be used in any industrial establishment under the
conditions described in their respective articles. In
industrial establishments only, where conditions of
maintenance and supervision ensure that only qualified persons
will service the installed cable tray system, any of the
cables in (1) and (2) shall be permitted to be installed in
ladder, ventilated trough, or ventilated channel cable
trays." You are correct in your assertion that
single-conductor power cables in solid bottom tray are not
permitted. The 1999 Code permits only single-conductor
cables "to be installed in ladder, ventilated trough, or
ventilated channel cable trays." This limitation changed with the 2002
edition. Proposal 8-21 in the Report on Proposals for the 2002 Code was accepted. The substantiation for the proposal
was "Cables are installed within solid metal enclosures
every day, i.e., conduit and wireway. There is no reason to
exclude solid bottom tray from containing these cables as long
as they are being installed by qualified individuals in
industrial establishments and the fill requirements are
consistent with the conservative numbers used for conduit and
wireway." Also, Article 318 became Article 392. With the
acceptance of these revisions, Section 392.3(b) states, in
part, "In industrial establishments only, where
conditions of maintenance and supervision ensure that only
qualified persons service the installed cable tray system, any
of the cables in 392.3(B)(1) and (2) shall be permitted to be
installed in ladder, ventilated trough, solid bottom, or
ventilated channel cable trays." The 2002 edition does
permit single-conductor power cables in solid bottom tray. Section 392.11 provides the ampacity
requirements for multiconductor cables and single cables rated
2000-volts or less in cable tray. 392.11(B) details the
requirements for single-conductor cables. Your question did
not specify a cable size. You will need to read all of
392.11(B) to determine which of the items meets your specific
needs. A new exception is added in the 2005
edition in Section 392.11(B)(3). Code-making panel 8 accepted
Proposal 8-291. The new exception is, "Exception: For
solid bottom cable trays the ampacity of single-conductor
cables shall be determined by 310.15(C)." The
substantiation for this proposal was: "The issue is the
ampacity of single-conductor cables in solid bottom cable
trays where the ventilation is restricted relative to ladder
and ventilated trough cable trays. The situation is somewhat
analogous to the condition of solid unventilated covers.
Section 392.11(B)(1) indicates a reduction in ampacity, as
given in tables 310.17 and 310.19 from 75 percent to 70
percent. These ampacity tables apply to single conductors in
free air. Subsections (2) and (4) of 392.11(B) derate the free
air ratings in 310.17 and 310.19 by 75 percent and are already
derated for solid bottom cable trays. Item (3) however, allows
the use of 100 percent of the free air ampacity ratings in
tables 310.17 and 310.19 if the cables are spaced a cable
diameter apart. Solid bottom cable trays will restrict the
free air flow to these conductors; therefore, the ampacity
should be determined under engineering supervision per
310.15(C)." As a result of this exception, the ampacity
of single-conductor cables in solid bottom cable tray may only
be determined by engineering supervision that utilizes the
formula in 310.15(C). The NEC is a living document that is
constantly changing to reflect changes in the electrical
industry. Article 392 is a prime example. Many changes have
taken place in 392 during the last three code cycles. That
process will continue during the coming cycles. Everyone is
encouraged to be an active participant in the process by
submitting proposals and comments and by being active in the
IAEI. — Wayne A. Lilly, CMP-08 | Return
to top | Question
8. What is the NEC spacing requirement when
installing .48 diameter, 4-conductor Belden 29500 variable
frequency drive cable in a lay-in wireway? — T.R. Answer 8. You
have brought up an interesting question for the use of the
Belden variable frequency drive (VFD) type cable and are
asking if this 29500 cable is allowed to be installed in
lay-in wireway trough. I think a couple of items need be clarified
about the Belden 29500 cable. This is a 16 AWG cable and is
being used to carry power from AC drive systems to AC motors
that may be located in harsh locations. When you consider a
VFD, the power associated with cable fed from the VFD to the
motor is coming off of an internal bussing that may operate at
up to 650 volts DC. In this case when we look at the
manufacturer’s (Belden) information listing from their
catalog, it shows a UL rating of 600 volts when used as tray
cable (TC) from Article 336 of NEC-2002, or as open
wiring as per Article 398 of NEC-2002, and has a 1000
volts rating UL/CSA for uses other than those listed above. Wireway has no voltage limitations as some
raceway types, but when VFD cable is installed in lay-in
wireway, the conditions for the installation requirements for
type TC cable has to be considered. The uses permitted in
336.10 are: (1) for power, lighting, control, and signal
circuits; and (2) it allows type TC cable to be used in cable
trays, or in raceways. There are no restrictions for uses not
permitted when installed in a lay-in wireway as per 336.12. The next consideration will be for the use
for a possible over 600-volt applications. The basic
requirements of Article 300, Wiring Methods, cover all wiring
methods for all wiring installations unless modified by other
articles. Additionally, Section 300.3(C)(1) and (2) provides
information for conductors of different systems. Section
300.3(C)(1) allows 600 volts, nominal or less. Conductors of
circuits rated 600 volts, nominal, or less, ac circuits, and
dc circuits shall be permitted to occupy the same equipment
wiring enclosure, cable, or raceway. All conductors shall have
an insulation rating equal to at least the maximum circuit
voltage applied to any conductor within the enclosure, cable,
or raceway. Section 300.3(C)(1) makes it clear that it
is the maximum circuit voltage in the raceway, not the maximum
insulation voltage rating of the conductors in the raceway,
that determines the minimum voltage rating required for the
insulation of conductors for systems of 600 volts or less. If
the installation is a 600 volts or less type of use for the
VFD cable and all other conductors contained in the lay-in
wireway are rated for the maximum operating circuit voltage in
the wireway, no conductor separation would be required. If the installation has mixed voltages of
600 volts or less and over 600 volts within a raceway or
wireway, then 300.3(C)(2) would have to be considered:
"Conductors of circuits rated over 600 volts, nominal,
shall not occupy the same equipment wiring enclosure, cable,
or raceway with conductors of circuits rated 600 volts,
nominal, or less unless otherwise permitted in (C)(2)(a)
through (C)(2)(e)." Section 300.3(C)(2)(d) states, "In
motors, switchgear and control assemblies, and similar
equipment, conductors of different voltage ratings shall be
permitted." If these are mixed conductors from the VFD
control assembly for motor(s) only for the power conductors
and the conductors have shielded insulation (Belden 29500 is a
shielded cable) for that system only, then no separation of
conductors would be required. If the operating voltage is over
600 volts, then the opening statement of 300.3(C) would not
allow the VFD type cable to be installed within a lay-in
wireway with other conductors and follow the installation
requirements of type TC cable. — James Imlah, CMP-8 | Return
to top | The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||