|
|
||
|
IAEI News>Focus on the Code >CMP-7
Question 1. I am trying to find a Code article or reference to the use of SE cable in conduit underground. Chapter 9 states that for multiconductor cables, you have to use the actual dimension. This is not a problem, because you just measure the outside diameter. My question is, Is USE cable listed for use in conduit underground? R.P. Answer 1. The
use of Type SE or USE in conduit either underground or aboveground is not
prohibited by the NEC. However, neither of these cable types is
listed for such use so the decision to accept or reject is up to the
authority having jurisdiction (AHJ). The following information may be helpful in
considering such a decision. There are two serious concerns with this type
of installation. The first is damage to the cable or individual conductors
as they are pulled into the raceway. The other is the added resistance to
heat dissipation. Both concerns can be addressed to some extent by using a
conduit one size larger than required in Chapter 9. This reduces the
friction of the pull, making it less likely that the conductors will be
damaged during installation, and provides a larger air space to dissipate
the heat buildup in the conductors under operating conditions. In general, such an installation is poor practice
and should not be permitted where there are more than two ninety-degree
bends in the run of raceway or where the circuit is expected to run at full
load (80 percent of rated ampacity) for any length of time. The sole
advantage to running SE cables in conduit underground is the ability to
replace them, if necessary, without excavating. Of course, the use of THHW
conductors in conduit provides this same advantage with none of the
drawbacks identified above and is probably more economical as well. T.E.
Trainor, CMP-7 | Return
to top | Question 2. Does this requirement include NM wiring in the basement
run between floor framing and upwards through the
subfloor for outlets, etc., on the first or second
floor? Rick Bowling Answer 2. Section 336-6 [334.15 in NEC 2002 ]
relates to installations where the nonmetallic-sheathed cable is exposed to
physical damage. If the NM cable comes through a floor into a wall, it is
not exposed and no additional protection is required. If the NM cable comes
through a floor (any floor) into an open area, it is exposed to physical
damage and additional protection is required. Tom Trainor, CMP-7 | Return
to top | Question
3. I am trying to find a Code article or reference to the use of SE cable in conduit
underground. Chapter 9 states that for multiconductor cables,
you have to use the actual dimension. This is not a problem,
because you just measure the outside diameter. My question is,
Is USE cable listed for use in conduit underground? R.P. Answer 3. The
use of Type SE or USE in conduit either underground or above
round is not prohibited by the NEC. However, neither of
these cable types is listed for such use so the decision to
accept or reject is up to the authority having jurisdiction (AHJ). The following information may be helpful in
considering such a decision. There are two serious concerns with this
type of installation. The first is damage to the cable or
individual conductors as they are pulled into the raceway. The
other is the added resistance to heat dissipation. Both
concerns can be addressed to some extent by using a conduit
one size larger than required in chapter 9. This reduces the
friction of the pull, making it less likely that the
conductors will be damaged during installation, and provides a
larger air space to dissipate the heat buildup in the
conductors under operating conditions. In general, such an installation is poor
practice and should not be permitted where there are more than
two ninety-degree bends in the run of raceway or where the
circuit is expected to run at full load (80 percent of rated
ampacity) for any length of time. The sole advantage to
running SE cables in conduit underground is the ability to
replace them, if necessary, without excavating. Of course, the
use of THHW conductors in conduit provides this same advantage
with none of the drawbacks identified above and is probably
more economical as well. T.E. Trainor, CMP-7 | Return
to top | Question
4. In 336-6(b), Exposed Work [NEC 1999 ], it
says, "
Where passing through a floor, the cable shall
be enclosed in rigid metal conduit, intermediate metal
conduit, electrical metallic tubing, Schedule 80 PVC rigid
nonmetallic conduit, listed surface metal or nonmetallic
raceway, or other metal pipe extending at least 6 in. (152 mm)
above the floor." Does this requirement include NM wiring in
the basement run between floor framing and upwards through the
subfloor for outlets, etc., on the first or second floor?
Rick Bowling Answer 4. Section
336-6 [334.15 in NEC 2002 ] relates to installations
where the nonmetallic-sheathed cable is exposed to physical
damage. If the NM cable comes through a floor into a wall, it
is not exposed and no additional protection is required. If
the NM cable comes through a floor (any floor) into an open
area, it is exposed to physical damage and additional
protection is required. Tom Trainor, CMP-7 | Return
to top | Question
5. I seem to be frequently involved in discussions
over the use of cable ties as a supporting means for MC cable.
Section 330.30 does not clearly state that cable ties can be
used as a support method. I am aware that cable ties are
clearly defined as an approved method in the following code
locations: 320.30, Armored Cable; 334.30, Nonmetallic-Sheathed
Cables; 338.10(B)(b), Service-Entrance Cable; and 340.10(4).
Could you give us your take on this subject? G. C. Answer 5. Section
330.30 of the 2002 NEC requires Type MC cable to be
supported and secured at intervals not exceeding 1.8 m (6 ft).
Section 300.11 also applies and requires cable assemblies to
be securely fastened in place. Section 320.30 allows cable
ties to be used to secure Type AC cable and does not allow
cable ties to be used to support Type AC cable. Sections
334.30, 338.10(B)(4)(b), and 340.10(4) also reference cable
ties for securing but not for supporting cables. Cable ties
are specifically mentioned in 2002 Code articles for
securing cable type wiring methods but not as the supporting
means. Gaylen Rogers, CMP-7 | Return
to top | The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||