|
|
||
|
IAEI News>Focus on the Code >CMP-2
Question
1. Is there NEC code that prohibits shared neutrals in lighting and
duplex branch circuits? This is one of the most
dangerous things for electricians working on 277-volt
lighting circuits. "No shared neutrals" was a
standard in the facility I was working in. Please let me
know if this is covered somewhere the NEC code. — T.V. a Answer 1. The Code defines a Multiwire Branch Circuit as
follows: "A branch circuit that consists of two or more ungrounded
conductors that have a voltage between them, and a grounded conductor that
has equal voltage between it and each ungrounded conductor of the circuit
and that is connected to the neutral or grounded conductor of the
system." This appears to be what you have described as branch
circuits with a shared neutral. Multiwire branch circuits are permitted by
Section 210.4 and can be used in dwelling units and other than dwelling
occupancies. There are conditions that have to be followed when using
multiwire branch circuits. Section 210.4(C) permits only line-to-neutral
loads to be supplied. Exceptions permit multiwire branch circuits to supply
only one utilization equipment and when the ungrounded conductors are opened
simultaneously by the branch-circuit overcurrent device. Section 210.4(B)
requires that the ungrounded conductors of a multiwire branch circuit in
dwelling units be simultaneously disconnected when the multiwire branch
circuit supplies more than one device on the same yoke. Section 210.7(C)
requires simultaneous disconnection of the ungrounded circuit conductors of
branch circuits when "more than one branch circuit supplies more than
one receptacle on the same yoke." These branch circuits may or may not
be multiwire branch circuits. Also Section 300.13(B) does not permit a device
connection, such as lampholders or receptacles to provide continuity when
the grounded conductor would be interrupted upon removal of the device. In
other words, the neutral has to be "pigtailed" when multiwire
branch circuits are used. There may be instances where multiwire branch circuits
should not be used. The Fine Print Note (FPN) of 210.4 warns that a
"shared neutral" or multiwire branch circuit may not be advisable
when nonlinear loads such as computer loads are encountered. Two-wire branch
circuits would be better than multiwire branch circuits where harmonic
currents are present. Electricity is dangerous whether you use a two-wire or multiwire branch
circuit, 120-volt or 277-volt and the electrical wiring should only be
serviced by a qualified person. — James W. Carpenter, CMP-2 | Return
to top | Question
2. I am an
electrical contractor, and one of my incorporated areas
has an inspector who says the laundry room must have a
separate circuit for just the washer, and that if we
install another outlet in the room for a convenience
outlet, it must be on another circuit. My interpretation
of 210.11 (C)(2) [NEC 2002] is that all the
outlets in the laundry room should be on the same
circuit. If I am not correct, would the second
(and any additional outlets) have to be on a 20- or
15-amp circuit, and would the washer outlet have to be a
single outlet? If I am correct, what can I use to
convince the inspector? B.T. Answer 2. Section
210.52(F) refers to laundry areas rather than a laundry room.
Section 210.11(C)(2) states that the laundry branch circuit is allowed to
supply outlet(s). “At least one additional 20-ampere branch circuit shall
be provided to supply the laundry receptacle outlet(s) required by
210.52(F)...” This section allows an additional outlet to be
installed for laundry equipment in the laundry area (for example, a plug
receptacle to be used for an iron or additional laundry equipment located
within the laundry area). The inspector’s interpretation that another
outlet installed in the laundry area for a convenience outlet would be
correct if the use is not for associated laundry equipment. The
interpretation by the authority having jurisdiction (inspector) would
determine the use of additional outlet(s) from the laundry branch circuit. The laundry area/laundry room can be supplied by
additional branch circuits/outlets of either 15- or 20-ampere circuits for
general use. However, the laundry receptacle outlet(s) is required by
210.11(C)(2) to be a 20-ampere branch circuit. —Ernie Broome, CMP-2 | Return
to top | Answer 3. At least one light outlet containing a
switch, or controlled by a wall switch, shall be installed where these
spaces are used for storage or contain equipment which requires servicing. Your first question was “Is a
pull-chain light fixture (luminaire) allowed?” The answer is yes, at least one lighting outlet
containing a switch or controlled by a wall switch shall
be installed at the usual point of entry to these
spaces. Your second question refers to the pull-chain light
fixture (luminaire) and where it can be located. It must
be located at the point of entry. The location must be
immediately located (occurring at once) as soon as you
enter the space. The distance of six or eight feet that
you refer to would not be immediately located (occurring
at once) as soon as you enter the space and would not be
acceptable according to 210.70(A)(3) of the NEC 2002. Note that the switch is on the pull-chain light
fixture. The string is not the switch. —Ernest S.
Broome, CMP-2. | Return
to top | Question
4. Retired as an electrician from Canada, I am
looking for some information on the use of split-circuit
duplex receptacles in U.S. kitchens over the last three
decades. These multiple-circuit receptacles have been
mandatory in our Canadian kitchens (countertops) since 1966
and I was wondering just how extensively they have been used
in the U.S., and whether they have ever been part of the National
Electrical Code. I do know that the U.S. now uses 20-amp
receptacles in their kitchens, but I am wondering if in the
past the split receptacles were used extensively. I would
appreciate any help you can give me in this area or steer me
to someone or some organization that might be able to help. —
B. F. Answer 4. I
will try to give you the information I have in regards to
split-wired receptacles. In the National Electrical Code 2002, Section 210.4 for Multiwire Branch Circuits permits
these to be used in dwelling units with certain restrictions
for safety measures. These restrictions are as follows: you must
use a means of disconnecting simultaneously all ungrounded
conductors; you must make sure that each circuit is being fed
from the same panelboard where the branch circuits originated;
and you must use a suitable handle tie across the two breakers
or a double pole breaker to disconnect the two circuits that
feeds the split-wired receptacle or equipment. These rules must be followed anytime two
ungrounded conductors of a multiwire branch circuit are
terminated on a receptacle of the same yoke. I can only speak
in our jurisdiction that this practice of split -wiring
receptacles is hardly ever used in kitchens or for equipment.This is a design issue that is totally up
to the electrical contractor or builder. I can tell you that
over the last 30 years of wiring and inspecting dwellings, I
may have seen it used only a few times.The requirement of split-wired receptacles
has never been a mandatory rule in the NEC. —
Ernie Broome, CMP-2 | Return
to top | Question
5. Is an area that has a 24" x 80" doorway and is L-shaped with approximately 33 square foot and
a height of 4', under a stairway landing, considered to be a storage
area that would require a switch and a light? — B.B. Answer 5. Review
210.70(A)(3) [NEC 2002], Storage or Equipment Spaces.
For attics, underfloor spaces, utility rooms, and basements,
at least one lighting outlet containing a switch or controlled
by a wall switch shall be installed where these spaces are
used for storage or contain equipment requiring servicing. At
least one point of control shall be at the usual point of
entry to these spaces. The lighting outlet shall be provided
at or near the equipment requiring servicing. As you have
indicated in your question, the space is used for storage and
is an underfloor space and thus should have a lighting outlet
installed. — Raymond W. Weber, CMP-2 | Return
to top | Question
6. Do a dishwasher and a garbage disposal have to
be on separate circuits? Can you have any lighting outlets on
with these? — E.F. Answer 6. Reference
110.3(b) [NEC 2002], Installation and Use. "Listed
or labeled equipment shall be installed and used in accordance
with any instructions included in the listing or
labeling." Thus, if the manufacturer specifies a separate
dedicated circuit for a dishwasher or garbage disposal, then
the response is yes.If a separate circuit is not indicated,
then we must review Section 210.19(A)(1), General.
"Branch-circuit conductors shall have an ampacity not
less than the maximum load to be served. Where a branch
circuit supplies continuous loads or any combination of
continuous and noncontinuous loads, the minimum branch-circuit
conductor size, before the application of any adjustment or
correction factors, shall have an allowable ampacity"
equal to or greater "than the noncontinuous load plus 125
percent of the continuous load." I would not consider a
dishwasher or garbage disposal to be a continuous load. Next,
we need to consider Section 210.23(A) 15- and 20-Ampere Branch
Circuits. "A 15- or 20-ampere branch circuit shall be
permitted to supply lighting units or other utilization
equipment, or a combination of both, and shall comply with
210.23(A)(1) and (A)(2)." Subsection (A)(1) states,
"The rating of any one cord-and- plug-connected
utilization equipment shall not exceed 80 percent of the
branch-circuit ampere rating." Subsection (A)(2) states,
"The total rating of utilization equipment fastened in
place, other than luminaires (lighting fixtures), shall not
exceed 50 percent of the branch-circuit ampere rating where
lighting units, cord-and-plug-connected utilization equipment
not fastened in place, or both, are also supplied." The final answer is that it can be done if
proper circuit ampacity is provided for and the system branch
circuit is designed as indicated. — Raymond W. Weber,
CMP-2 | Return
to top | Question
7. Is a 28-amp
electric clothes dryer plugged in to a 30-amp individual
branch circuit in compliance with the permissible loads
of NEC 210.23, or does the 80 percent rule apply? — E.K. Answer 7. Section
210.23 [NEC 2002] states, "In no case shall the load exceed the
branch-circuit ampere rating. An individual branch circuit shall be
permitted to supply any load for which it is rated. A branch circuit
supplying two or more outlets or receptacles shall supply only the loads
specified according to its size as specified in 210.23(A) through (D) and as
summarized in 210.24 and Table 210.24." Section 210.23(B) states,
"30-Ampere Branch Circuits. A 30-ampere branch circuit shall be
permitted to supply fixed lighting units with heavy-duty lampholders in
other than a dwelling unit(s) or utilization equipment in any occupancy. A
rating of any one cord-and-plug-connected utilization equipment shall not
exceed 80 percent of the branch-circuit ampere rating." Thus, the question asks if a 28-ampere load is acceptable
on a 30-amp individual branch circuit, and the answer is yes, as long as
that is the only utilization equipment on that circuit with one outlet or
receptacle. The 80 percent rule applies when two or more outlets or
receptacles are installed per 210.23(A) through (D). — Raymond W. Weber | Return
to top | Question
8. I've
recently had an experience with the local inspector
regarding arc-fault circuit-interrupter (AFCI) breakers.
He tells me that I cannot put a ground-fault
circuit-interrupter receptacle on a circuit protected by
an AFCI breaker, unless it happens to be on the end of
the branch circuit. He quotes Section 210.12(B). My code
makes no mention of this, by any stretch. I dealt with
this issue years ago when arc faults were referenced in
the last Code. This raised a question in my mind
back then so I contacted the manufacturer. They said
there were no problems with such an application. Can
anybody give me any guidance or offer any advice. —
J.R. Answer 8. As
much as I hate to say it, the inspector is wrong (hurts me deeply). There is
nothing in Section 210.12(B) [NEC 2002] that makes a GFCI receptacle
installed at any point on that AFCI-protected branch circuit for outlets
installed in dwelling unit bedrooms a code violation. As fast as the
electrical industry and products are changing, we all need to attend update
training and seminars to stay current with the Code requirements. —
Raymond W. Weber | Return
to top | Question
9. I am in the process of preparing
to adopt the 2002 NEC. I have run across one Code change
that appears to be causing other jurisdictions some concern
that I will outline below. Section 210.12 now requires all branch
circuits that supply 125-volt, single-phase, 15- and 20-ampere
outlets to be arc-fault protected. Typically, the smoke
detectors are served by a branch circuit installed solely for
that purpose. Although they serve an outlet in the bedroom,
was the change intended to require smoke detectors to be
arc-fault protected? — B.C. Answer
9. As stated in Section 210.12(B),
"all branch circuits that supply 125-volt, single- phase,
15- and 20-ampere outlets installed in dwelling unit bedrooms
shall be protected by an arc-fault circuit interrupter listed
to provide protection of the entire branch circuit." First, we must go to the definition of outlet in
Article 100, which is: "A point on the wiring system at
which current is taken to supply utilization equipment." The smoke detector is an outlet by definition and is installed
in the bedroom. Panel 2 in its deliberations of the 2005 NEC ROP and ROC had a number of code change proposals and
subsequent comments to exempt the smoke detectors from the
requirement. As was discussed at the code panel
meetings, even though that smoke detector has a battery
back-up system and may not be easily accessible, it would
still need AFCI protection. Comments about nuisance tripping
of the breaker have not been widely experienced in the field.
The panel even had a proposal to exempt an outlet in the
bedroom area that was for the use of health care related
diagnostic equipment, that was supported in the ROP phase and
then deleted in the ROC phase because of the standard for the
equipment manufacturers to have a leakage current level well
below the plateau of the AFCI functioning. This is a safety
feature that is, in my opinion, by far the best deterrent next
to GFCI for protecting homes and families from potential
fire-related losses.—Raymond W. Weber, CMP-2 Technical Editor’s Note: The mention of smoke detectors in this reply is intended to
reference single station smoke alarms connected to the branch
circuit. Smoke detectors that are part of a fire alarm system
are covered by rules in Article 760. Revisions in 760.21 and
760.41 exempt power sources for fire alarm circuits from being
supplied through AFCIs. The circuits addressed in the question
are branch circuits as defined in Article 100 not fire alarm
circuits or power source circuits for fire alarm circuits. See
the scope of Article 760 and the definition of fire alarm
circuit for additional information. | Return
to top | Question
10. I would like to know what the
intent of the Code was concerning outdoor receptacle
location. Is an outlet required to be accessible to a person
that is standing on the ground? Does a receptacle on the deck
or porch that can’t be reached from the ground/grade fulfill
the Code requirements? — G. D. Answer
10. The answer to the first
question the answer is yes, and the answer to the second
question the answer is no. The Code reference is
210.52(E), Outdoor Outlets [2002 NEC]. For a one-family dwelling, and each unit of
a two-family dwelling that is at grade level, at least one
receptacle outlet accessible at grade level and not more the
2.0 m (6 1/2 ft.) abovegrade shall be installed at the front
and back of the dwelling. See 210.8(A)(3) which addresses the
GFCI protection requirement. The term accessible is
used and by definition when applied to equipment and not
wiring methods states, "Admitting close approach; not
guarded by locked doors, elevation, or other effective
means." Notice the term elevation is used and in
the Code the panel has indicated at grade level and not
more than 2.0 m (6 1/2 ft) abovegrade. No minimum dimension
was set or given, but it should be reachable by standing on or
at grade and not exceeding the designated height. Oftentimes
railings are treated as if they were solid walls, and cannot
be reached through to get at a required receptacle location
and therefore do not meet the Code intent. Remember the requirement in Section
406.8(B)(1) for outdoor receptacles to have the (bubble) or in
use cover and not just a standard weatherproof cover that does
not enclose the attachment plug when it is inserted. It should
be noted that this is my opinion and not an official position
of NFPA or CMP-2. — Raymond W. Weber, CMP-2 | Return
to top | Question
11. Would it meet the intent of
Section 210.12 to exclude AFCI protection for a 120-volt
circuit feeding the smoke detector outlets in dwelling unit
bedrooms? — E. D. Answer
11. According to both the 2002 and
the 2005 NEC directives, the answer would be no, it
would not. All outlets in the bedroom are to have AFCI
protection; the smoke alarm in the bedroom area meets the
definition of an outlet and therefore requires the AFCI
protection. At the code panel meeting, this issue was debated
and proposals and comments were submitted to CMP-2 for
exempting the smoke alarm outlet in the bedroom, but none
received the majority vote by the panel to make an exemption
to the AFCI requirement. — Raymond W. Weber, CMP-2 | Return
to top | Question
12. In the 1999 NEC, under the section for
the requirements for kitchen island outlets, the Code says
that only one outlet is needed for a space 12" x
24". It then goes on to say that island counter space
divided by a sink, stove or refrigerator is considered
separate counter spaces. Assuming that the outlet is allowed
to be mounted below the counter, on a 4' x 6' island with a
small vegetable sink 24" in from the end, does the Code allow only one outlet to be installed 4' away and on
the opposite corner where it would have been allowed if there
were no sink? What if there was also a stove, does this
now create three 12" x 24" spaces, or does the
stove/sink have to divide the island counter top completely? — K. K. Answer
12. Sections 210-52(C)(2) and (4) [1999 NEC]
address your question. The answer would be that yes, two would
be required; with one being installed on either side of the
sink/stove top unit. You may wish to refer to the 2005 NEC, 210.52(C)(2) and (4) and Figure 210.52 for information that
may apply in your jurisdiction in the future. Under that
concept and given certain dimensions, you may have a
requirement for receptacles behind sinks/stove units located
adjacent to wall areas but not on the island areas. —
Raymond W. Weber, CMP-2 | Return
to top | Question
13. How are cord-and-plug connected window air
conditioner loads handled in sizing services? Should they be
considered as fixed in place equipment (like a central air
conditioner)? Are they part of the 3-watt-per-square-foot
lighting load (like any other cord-and-plug-connected
appliance)? I’m upgrading an existing multi-tenant apartment
house to provide additional circuits and 120-volt receptacles
for the ten-ant’s window air conditioners and I am unclear
how to approach the load calculations for the building. —
G. O. Answer
13. The load is definitely not part of the
3-watt-per-square-foot lighting load, even though it is
cord-and- plug-connected. Under certain conditions, it may
even be a continuous load for long durations of time. I would
identify the units to be utilized with its load requirements
and consider them as fixed equipment. Thus ensuring that a
worst-case scenario can be handled via sufficient electrical
system capacity. I would use 220.4(A) [NEC-2002] as a
guide. — Raymond Weber, CMP-2 | Return
to top | The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||