|
|
||
|
IAEI News>Focus on the Code >CMP-18
Question
1. I am proposing to use Lucifer low-voltage strip
lights with lens covers (see image
1 and image
2) within wardrobe cabinets (see attached drawing).
Does 410-8 [NEC 1999] apply to this application
as though it were a closet? Any assistance would
be most appreciated. — Fred Fargetstein Answer 1. This
question is asking for a clarification on the application of NEC 410-8. To rephrase the question: Do the installation requirements of NEC 410-8,
Fixtures in Clothes Closets, apply to wardrobe cabinets too? In general, the
answer is no. Article 410 covers lighting fixtures and lighting
installations. Section 410-8 applies to the installation of lighting
fixtures in clothes closets.” This section consists of several
subsections, which provide a definition of storage space, information on the
type of lighting fixtures permitted and not permitted in clothes closets,
and the acceptable locations for the installation of lighting fixtures in
clothes closets. Although 410-8 is not specific to wardrobe
cabinets, the answer to the question is within subsection 410-8(a) —
definition of storage space. “Storage space shall be defined as a
volume bounded by the sides and back closet walls and planes extending from
the closet floor vertically to a height of 6 ft (1.83 m) or the highest
clothes-hanging rod and parallel to the walls at a horizontal distance of 24
in. (610 mm) from the sides and back of the closet walls respectively, and
continuing vertically to the closet ceiling parallel to the walls at a
horizontal distance of 12 in. (305 mm) or the width of the shelf, whichever
is greater.” This definition provides a reasonably good mental picture of
a storage space. With some clarification, we can determine if this space
applies to wardrobe cabinets too. To do this, a little reasoning is in
order. According to the definitions of “wardrobe” and
“closet” in Webster's Dictionary, it is reasonable to conclude
that a wardrobe and closet are one in the same. It is also reasonable to
conclude, based on the information in the sketch submitted with this
question, that the wardrobe cabinet is for hanging clothes. Therefore, it is
reasonable to conclude that a wardrobe cabinet is indeed a clothes closet.
Knowing this, how can the answer to the question be no? The clothes closets that the NEC addresses
are a permanent part of the building or structure. Clothes closets are
constructed of the building or structure walls and ceiling. The walls are
the sides of the building or room connecting the floor and ceiling; the
ceiling is the overhead inside lining of the room; and, the closet is the
space surrounded by the walls. Wardrobe cabinets are not part of the
permanent building or structure. Wardrobe cabinets are household or
commercial furnishings that may or may not be illuminated. Except for office
furnishings, the NEC does not cover installation requirements for
lighting fixtures in these furnishings. Lighting fixtures installed in these furnishings
fall under the purview of the appropriate product safety standard. Clothes
closets that the NEC addresses and wardrobe cabinets are not one in
the same. Wardrobe cabinets are simply furnishings for the building or
structure. It may be wise to consult the cabinet manufacturer, the lighting
fixture manufacture, and the appropriate product safety standard for the
specific requirements of lighting fixtures in furnishings. This is
especially important where the furnishing’s intended use is for hanging
clothes. Fire is one of the major concerns with lighting fixtures in clothes
closets. Obviously, lighting fixtures and combustibles confined within any
small space can lead to a fire hazard. Naturally, lighting fixtures get hot during
operation. Many require adequate ventilation and installation locations
where they are not confined. Some require installation on an insulated wall
or ceiling, or on a noncombustible surface. Lighting fixtures are readily
available that can be installed in these cabinets with ease. Knowing this, a
warning of “let the buyer beware” may be in order. Many of these
lighting fixtures are not intended for installation or use in enclosed
spaces. Always read and follow the manufacturers' installation and use
instructions included with lighting fixtures. As a final note, keep in
mind that the NEC does not address every
installation scenario that may arise in the field. This
would be impossible. In those instances, a judgment call
by the authority having jurisdiction is usually
necessary. I hope this response provides some
clarification to the application requirements of 410-8.
If not, it never hurts to use good common sense too! —
Lanny McMahill, CMP-18 | Return
to top | Question
2. The
following question has come up in local Code discussions and as an inspector, I do not have a clear
answer. I have looked in the U. L. White book under
“Incandescent Recessed Luminaires” (IEZX), but did
not find an answer. May thermal protected (type T.P.)
recessed can lights (luminaires) be installed in a
cathedral (i.e. slanted) ceiling? If yes, should the
thermal protection element be on the high or low side of
the can? Your assistance with this would be appreciated. — A.N. Second,
the thermal protection has nothing to do with the
mounting position or orientation of a recessed
incandescent luminaire. Disregarding the exceptions to National
Electrical Code (NEC) 410.65(c), all recessed
incandescent luminaries, regardless of mounting position
or orientation, shall have thermal protection. It makes
no difference if the thermal protection element is “on
the high or low side of the can.” If installed per the
listing and labeling, the thermal protection element
will perform properly. Third, although this information is not readily
available in “Underwriters Laboratories White book,”
and unless there are restrictions by the manufacturer's
installation instructions or marking on the luminaire,
ceiling mounted luminaries can be wall mounted too.
Luminaires identified for wall or ceiling mounting,
conform to the test standard requirements for ceiling
mounted luminaries. Luminaires tested for wall mount
installation only, are marked “Wall Mount Only.”
Again, with these caveats in mind, the answer to the
question is yes. Feel comfortable installing a recessed
incandescent luminaire in a slanted position in a
cathedral ceiling. The recessed luminaire will perform
properly whether mounted in the ceiling or wall or
somewhere in between if installed per its listing or
labeling. Where properly installed, there should be no
concern with the orientation of the luminaire's thermal
protection element. — Lanny McMahill, CMP-2 | Return
to top | Question
3. I am hoping
that you can settle an ongoing debate that we are having
in our office. Our controversy involves the placement of
receptacle outlets in the area around bathtubs and
showers. NEC 410.4(D) [2002], Bathtub
and Shower Areas, provides a specific area around tubs
and showers that certain types of luminaries are not
permitted to occupy. NEC 406.8(C), Bathtub and
Shower Space, restricts the installation of receptacles
within a tub or shower space, but does not define the
boundaries of this space. This brings me to our question: Based on the area referred to in 410.4(D) and the
space referred to in 406.8(C), are both of these
sections referring to the same physical space? In the Illustrated Guide to the National
Electrical Code, 1999 edition, by Charles Miller, he
treats both of these areas the same and states that no
receptacle outlet is permitted in the space. What is your interpretation on this issue? — W.S. Answer 3. I
am not sure I can settle the debate, but I will attempt
to provide some guidance for a reasonable conclusion In the Manual of Style for NFPA
Technical Committee Documents, Section 3.2.1.2
states, “Spelling and definitions of general words and
terms shall follow Webster's Collegiate Dictionary, 10th
edition.” Section 3.2.2.3 states, “When a standard
definition is needed, Webster's shall be utilized where
the meaning is correct and accurate as used in NFPA
documents.” Section 410.4(D), Bathtub and
Shower Areas, addresses luminaires (fixtures) in
specific locations. It states that “No parts of
cord-connected luminaires (fixtures), hanging luminaires
(fixtures), lighting track, pendants, or
ceiling-suspended (paddle) fans shall be located within
a zone measured 900 mm (3 ft) horizontally and 2.5 m (8
ft) vertically from the top of the bathtub rim or shower
stall threshold. This zone is all encompassing and
includes the zone directly over the tub or shower
stall.” Section 406.8(C), Bathtub and
Shower Space, addresses receptacles in damp or wet
locations. It states, “A receptacle shall not be
installed within a bathtub or shower space.” Webster's Dictionary defines space as “a limited extent in one, two, or three
dimensions.” Working space is perhaps a
good example of the use of the word space. Working space
is given as a depth, width, and height — three
dimensions. Webster's defines zone as, “a region or area set off as distinct from
surrounding or adjoining parts.” Hazardous (classified) locations are a good
example of the use of the word zone. Zone is used extensively for classifying
hazardous locations in distinct areas. Knowing this, a reasonable
conclusion is that the words space and zone do not have
the same meaning. Space is less defined and zone is more
defined. However, if we refer to 225.19(E), Zone for
Fire Ladders, it would appear that space and zone are
one in the same. Section 225.19(E) states in part that,
“. . . overhead lines shall be arranged, where
practicable, so that a clear space (or zone) at least
1.8 m (6 ft) wide will be left either adjacent to the
buildings . . .” In this case, a reasonable conclusion
is that space and zone have the same meaning. Where does this lead us? Where the
word space is used in the Code, it allows for
some flexibility and judgment in code enforcement (i.e.,
receptacles along the floor line of a wall space); it is
less stringent. Where
the word zone is used in the Code, it does not
allow for the same flexibility and judgment in code
enforcement (i.e., hazardous (classified) locations); it
is more stringent. I hope this provides some guidance
for a reasonable conclusion. If you would like to debate this issue further, I
would suggest throwing the word area into the mix
too! — Lanny McMahill, CMP-18 | Return
to top | Question 4. I am
employed with the Maryland State Fire Marshals Office and I do
the electrical testing for them. The University of
Maryland called me with a question regarding the 2002 NEC.
The question dealt with 110.31(A). They were inquiring
if this applies to all electrical rooms or new
installations. They were also wondering why this code
change came about. The concern that they have is
partially due to an incident in the fall at their
facility. There was a fault in some switchgear in one of
their electrical rooms that resulted in a fire, and a fatality
occurred. Now they are going back and
evaluating all of their equipment and electrical closets
and researching the Code on it and finding that most of
the areas do not have the three-hour rating required by the
2002 NEC. Can you shed some light on this for me
as I am under the impression that it applies to new
construction and any major modifications? — M. C.
Answer 4. First,
I am sad to hear that an electrical incident resulted in a
fatality. Since you did not indicate the type of electrical
testing you perform for the Fire Marshall’s office, I will
begin with a note of caution. It is imperative that one be
familiar with NFPA Standard 70E and that one have the
appropriate safety training on the hazards involved when
performing any type of electrical testing. It is also
necessary to have the required skills and knowledge in the
installation, use and maintenance of the electrical system.
These factors are important when working on any electrical
system, but they are especially important when working on
equipment over 600 volts. Only qualified persons should
service such systems! Second, to address your questions, a
minor clarification is in order. National Electrical Code Article
110 provides the general requirements for electrical
installations, and Part III applies to electrical
installations over 600 volts, nominal. Subsection 110.31(A)
addresses the fire resistivity of electrical vaults. This
subsection provides specific information on the construction
requirements for an electrical vault. Subsection 110.31(A)
only applies where a vault is required for the electrical
installation. If the electrical equipment is enclosed, such as
in metal-enclosed switchgear, unit substations, pull boxes,
raceways, etc., a vault may not be required. Your question is asking if 110.31(A)
applies to all electrical rooms or new installations, and why
this code change came about in 110.31(A). Does 110.31(A) apply to all
electrical rooms? No. The word "room" typically
means a room within a building or structure. Subsection
110.31(A) only applies where an electrical vault (room) is
required within a building or structure. For installations
over 600 volts, an electrical vault is required where live
parts must be guarded against accidental contact or where
exposed service-entrance conductors are installed within a
building or structure. The electrical vault is the enclosure
for the live parts and conductors. A good example of this is
an outdoor substation and switching yard. Outdoor substations
and switching yards are installed in enclosed fenced-in areas.
There is no need for a fire resistive electrical vault as
there is no potential fire or explosion hazard to a building
or structure. The live parts require protection from
accidental contact — a fence or other suitable enclosure
accomplishes this. If this substation and switching yard were
in a building or structure, a fire resistive electrical vault
would be required. Does 110.31(A) apply to all new
installations? Generally, yes. Subsection 110.31(A) applies to
over 600 volt installations where an electrical vault is
required. An electrical vault is required for specific
installations, such as where live parts must be guarded or
exposed service entrance conductors are installed in a
building or structure. Why the code change to Section
110.31? The 1999 NEC, Section 110-31, Enclosures for
Electrical Installations, mentioned "electrical
installations in a vault." A fine print note (FPN) after
the section referred the user to Article 450 for construction
requirements for transformer vaults. The reference to
transformer vaults was confusing and the FPN was
unenforceable. To eliminate this confusion, it became obvious
that the construction requirements for electrical vaults
needed to be included in Article 110. Therefore, 2002 NEC,
Section 110.31(A), Fire Resistivity of Electrical Vaults, came
about. The requirements in 110.31(A) simply mirror the
requirements in Article 450 for a transformer vault.
Realistically, the intent of the code did not change, only the
usability. I hope my comments will assist you in
evaluating the electrical system for the facility and that
they provide reasonable guidance and clarification regarding
110.31(A). I also encourage you to be careful around over
600-volt systems and see that only qualified persons service
these systems! — Lanny McMahill, CMP-18 | Return
to top | Question 5. I have seen many electricians using their
side-cutting Klein pliers as strippers even though they do not
have a manufactured stripping hole. Is this considered a
legal or safe practice? If you want to stir up a hornet’s
nest, just challenge a group of them on this. — P.H. Answer 5. It
is common knowledge that most electricians have been guilty of
stripping conductor insulation with their side cutters at one
time or another, and some are good at it too. Is this
considered a legal or safe practice? Since a "yes"
or "no" response is out of the question, a little
deliberation is in order. Is this a legal practice? Section 110.12,
Mechanical Execution of Work, requires that electrical
equipment be installed in a neat and workmanlike manner.
Workmanlike is not defined in the NEC; however, Webster’s
defines it as "worthy of a good workman" or
"skillful." The word "craftsman" comes to
mind too. Based on Webster’s definition, it leads one to
surmise that workmanlike is in the eyes of the beholder. In
other words, what looks good to one person may be atrocious to
another. It should also be understood that the
proper use of any tool is a work practice issue. Work practice
issues are not addressed in the NEC. Therefore, the use
of an incorrect tool for any job has nothing to do with being
a legal practice. It has everything to do with being a good
work practice. Obviously, using side cutters for stripping
conductor insulation is not a good work practice. Is it a
legal practice? Only a craftsman can answer this question. Is this a safe practice? Section 110.12(C)
states, "There shall be no damaged parts that may
adversely affect safe operation or mechanical strength of the
equipment.…" Using an improper tool on any part or
equipment could easily affect safe operation. A damaged
conductor has the potential of creating a high impedance
current path; damaged conductor insulation could easily
subject a person to exposed live parts. Either situation is
undesirable and may adversely affect the safe operation of the
equipment. In addition, it is fair to note that not
too many tool manufacturers or training organizations would
recommend using side-cutting pliers as a stripping tool. Most
would train and advise to use the correct tool for the job at
hand. An analogy of this is asking a carpenter to do trim work
using a chain saw. Sure, the chain saw will do the job, but
the outcome may not be what was expected. So, is using
side-cutters as a stripper a safe practice? Definitely not! Always use the proper tools for the
installation or application and continue to learn and grow as
it can only lead to a safe and code compliant installation!
For those electricians good at stripping conductor insulation
with their side-cutters, keep-in-mind that bad habits are hard
to break. That should stir up a hornet’s nest too. —
Lanny McMahill, CMP-18 | Return
to top | Question 6. I have a question regarding 410.8(C). Is it permissible to use a fluorescent bulb in a recessed can and still meet the Code? I see no exceptions for this. — W. A. Answer 6. In response to your question, a fluorescent lamp in an incandescent luminaire does not make the incandescent luminaire fluorescent. Looking at 410.8(D), the Code uses wording to help the reader realize that the intent is to limit the proximity of an incandescent fixture to 12 inches from the storage space. Notice the use of the word fixture in this section. The problem is that while the inspector is on scene the fixture contains a fluorescent lamp; after the bulb runs its course of life and ceases to illuminate, there is no guarantee that an incandescent bulb could not be placed in the fixture causing a code violation. Note that there are fluorescent luminaires of the recessed type on the market that could be used here as the design of the fixtures precludes the use of an incandescent bulb. — Amos D. Lowrance Jr., CMP-18 | Return
to top | The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||