|
|
||
|
IAEI News>Focus on the Code >CMP-16
Question
1. Are listed enclosures/
boxes required to house low-voltage equipment and
devices in exterior locations, exposed to the weather?
The project was designed and is being constructed under
the 1993 NEC (1995 California Electric Code). Background. A low-voltage personal alarm system is being installed.
The system involves radio FM frequency locators and
low-voltage repeater devices installed outside, exposed
to the weather, in nonmetallic enclosures/boxes, and
infrared transmitter devices installed in metal
enclosures/boxes. The design calls for all the
low-voltage interior and exterior wiring to be installed
in conduit except where protected plenum wiring is
applicable. The
“Personal Alarm System” is a security system which
uses infrared (IR) and FM radio frequency (RF) reception
and repeater equipment. The IRs are hard-wired. Most of
the RFs are hard-wired, but some are powered by
photovoltaics. The repeaters are hard-wired and relay
signals to the control system. The system has been
identified as Class 2 wiring under Article 725. We
understand that Class 2 wiring is of such low voltage
that it is exempt from Article 300, Wiring Methods;
however, the project design requires (for protection
from abuse, vandalism, weather and ultraviolet
degradation) that the wiring and equipment be installed
in conduit, boxes and enclosures. Even though Class 2
may be exempt, do Code requirements for listing
apply to conduit, boxes and enclosures if they are used? The
manufacturer of the low-voltage equipment has provided
unlisted nonmetallic and metal enclosures for their
devices. The enclosures have been cited by the
inspection agency as needing to be listed, with
reference to NEC 110-3, Examination,
Identification, Installation and Use of Equipment, and
to 370-15, Damp, Wet or Hazardous Locations. The
manufacturer and designer have responded that listed
enclosures are not required by the Code. They
have cited 300-1(a), Exception No. 2, which states,
“Only those sections referenced in Article 725 shall
apply to Class 1, Class 2, and Class 3 circuits.” Article 725 includes Class 2 low-voltage wiring circuitry, and
appears silent on conduit and enclosure requirements.
The manufacturer and designer’s conclusion is that if
not specifically addressed in Article 725, the
requirements of Article 300, including 300-15, Boxes or
Fittings – Where Required, do not apply. Therefore
they maintain that Article 370 does not apply since
370-1, Scope, refers to 300-15. — M.M. Answer 1. According to
the 1993, 1996, 1999, and 2002 NEC, 90-3, Code
Arrangement, “...Chapters 1 through 4 apply except as
amended by Chapters 5, 6 and 7 for particular
conditions.” Section
300-1(a), All Wiring Installations. This article covers
wiring methods for all wiring installations. Exception
No. 2 states: “Only
those sections referenced in Article 725 shall apply to
Class 1, Class 2 and Class 3 circuits.” This exception was deleted in the 1999 and 2002 NEC. Therefore
370-15 of the 1993 and 1996 NEC do not apply, but
do apply in the 1999 NEC and under 314.15 of the
2002 NEC. Since the project design requires more than the minimum
code as stated, the authority having jurisdiction may
exercise his authority under 90.4, Enforcement, by
requiring 110.3, Examination, Identification,
Installation, and Use of Equipment, to be followed. —Larry
Chan, CMP-16 | Return
to top | Question 2. I am trying to find information regarding
telecommunications conduit placement within a
telecommunications room with regards to the placement of the
electrical conduit within that same room. Does the NEC address this situation similar to what is found in NEC
800.10(A)(1)? For example: electrical conduit associated/not
associated passing through a telecom room, is our conduit
required to be below the electrical conduit? — S. W. Answer 2. The 2002 NEC does not
address the situation given. No specific distances are
required between the electrical and the telecommunications
conduits — associated or not associated. A room housing
telecommunications equipment and wiring is a building design
issue. — Larry Chan, CMP-16 | Return
to top | The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||