Featured Images
Question 1
Application of NFPA 70, Article 701, to municipal fire stations

Question 2
Wiring Fire Pumps Properly
 
 
 
 
IAEI News>Focus on the Code >CMP-15
Focus on the Code Questions for CMP-15
The Focus on the Code column is intended to assist our readers and members in understanding the requirements of the National Electrical Code. Our Code consultants consists of IAEI representatives on the CMP-15 panels of the NEC and other selected experts. 


Question 1. I am looking for some informal assistance in the application of NFPA 70, Article 701, to our municipal fire stations. These stations have residential quarters and are manned 24 hours a day. I have taken the position that standby power to a fire station is necessary for fire fighting operations, communications, and equipment. I have used other jurisdictions, Red Cross disaster training, NEC 701-2(FPN) [1999 NEC], as well as my own judgment to arrive at this conclusion. That position is being questioned.

The plans show a generator feeding the stations that is not adequate for the entire load. No load shedding is provided and the generator replaces the utility supply through an automatic transfer switch. The submitter wants to call the generator at each station an optional standby system per NEC Article 702. I have asked for load shedding or an alternate design as called out by 701-6.

Are there any other guidelines or advice you can provide me to help justify a decision when backup power to a fire station should be legally required or optional standby power? Thank you. — S.D.

Answer 1. The scope of Article 701 covers the provisions that apply to the electrical safety for the installation, operation, and maintenance of legally required standby systems to supply power for illumination or power when the normal electrical supply or system is interrupted.

By definition, legally required standby systems are those systems required and so classed as legally required standby by municipal, state, federal, or other codes or by any governmental agency having jurisdiction. That means that the other codes adopted by any agency having jurisdiction list the requirements for the installation of a legally required standby system. These are normally building codes such as NFPA 5000, Section 12.8 and 12.9; NFPA 101, Sections 14.29, 15.2.9, and 7.9; and the International Building Code.

The NEC covers how to install the emergency system, test, and maintain the systems. All requirements as to what items are connected to the legally required standby system are normally reflected in the building code or other adopted life safety requirements.

With regards to your reference to Article 701.2(FPN), if you will review Article 90.5(C), you will see that this is explanatory material for informational purposes only and is not enforceable as requirements of this Code.

I hope this helps in you understand the requirements in the National Electrical Code. — Robert Duncan, CMP-15

| Return to top |


Question 2. How can I find information on how to wire fire pumps properly? — A.N.

Answer 2. NFPA 20, Stationary Pumps for Fire Protection, Chapter 6, requires all electrical equipment and installation methods to comply with NFPA 70, National Electrical Code, Article 695, and other applicable articles.

 Article 695.1 Scope.

 (A)  Covered. This article covers the installation of the following:

 (1)  Electric power sources and interconnecting circuits

(2)  Switching and control equipment dedicated to fire pump drivers.

NFPA 20, Stationary Pumps for Fire Protection, deals with the selection and installation of pumps supplying water for private fire protection. This standard does not cover the requirements for installation wiring of fire pumps.

I’m sure you already know the above information, so I will try to list some of the concerns in wiring a fire pump.

One of the main items in wiring a fire pump is that it has a reliable source of power. Check with the authority having jurisdiction on his interpretation of what he will approve. The power source shall be arranged so that a fire at one source will not cause an interruption at the other source, see NFPA 20 for those requirements.

Make sure that a listed fire pump, transfer switch, fire pump controller, or a combination controller and transfer switch are used in the installation.

The overcurrent devices shall be selected or set to carry indefinitely the sum of the locked-rotor current of the fire pump motor and the pressure maintenance pump motor and the full-load current of the associated fire pump accessory equipment when connected to the power supply.

The disconnecting means shall be identified as suitable for use as service equipment and be lockable in the closed position. Power circuits and wiring methods shall comply with the requirements in 695.6(A) through (G).

Controllers and transfer switches for electric motor-driven fire pump controllers and power transfer switches shall be located as close as practicable to the motors that they control, and shall be within sight of the motors, and shall be located or protected so that they will not be damaged by water escaping from pumps or pump connections.

External control circuits that extend outside the fire pump room shall be arranged so that failure of any external circuit shall not prevent the operation of a pump from all other internal or external means. No undervoltage, phase-loss, frequency-sensitive, or other sensors shall be installed that automatically or manually prohibit actuation of the motor contractor. The only exception is that a phase-loss sensor shall be permitted only as a part of a listed fire pump controller.

Control conductors installed between the fire pump power transfer switch and the standby generator supplying the fire pump during normal power loss shall be kept entirely independent of all other wiring. They shall be protected to resist potential damage by fire or structural failure. They shall be permitted to be routed through a building encased in 2 inches of concrete or within enclosed construction dedicated to the fire pump circuits and having a minimum 1-hour fire resistance rating, or circuit protective systems with a minimum of 1-hour fire resistance, and shall be installed in accordance with their listing.  Robert C. Duncan, CMP-15

| Return to top |


The views of the authors of Focus on the Code and the editor are provided solely as a public service. 

The views expressed are not the official position of NFPA, the NEC Correlating Committee or any of its panels, IAEI, IAEI News, or the author's employers. Nor are they intended to represent a formal or informal interpretation of the NEC

 

 

Get Focused!

Articles 90, 100, 110, Annex A, Annex G
Articles 210, 215, 220, Annex D, Examples 1-6
Articles 300, 590, 720, 725, 760, Chapter 9, Tables 11(a) and (b), Tables 12(a) and (b)
Articles 225, 230
Articles 200, 250, 280, 285
Articles 310, 400, 402, Chapter 9 Tables 5 through 9, Annex B
Articles 320, 322, 324, 326, 328, 330, 332, 334, 336, 338, 340, 382, 394, 396, 398
Articles 342, 344, 348, 350, 352, 353, 354, 356, 358, 360, 362, 366, 368, 370, 372, 374, 376, 378, 380, 384, 386, 388, 390, 392, Chapter 9 Tables 1-4, Annex C
Articles 312, 314, 404, 408, 450, 490
Articles 240, 780
Articles 409, 430, 440, 460, 470, Annex D, Example D8
Articles 610, 620, 625, 630, 640, 645, 647, 650, 660, 665, 668, 669, 670, 685, Annex D, Examples D9 through D10
CMP-13
Articles 445, 455, 480, 490, 690, 692, 695, 700, 701, 702, 705
Articles 500, 501, 502, 503, 504, 505, 506, 510, 511, 513, 514, 515, 516
Articles 517, 518, 520, 525, 530, 540
Articles 770, 800, 810, 820, 830
Articles 422, 424, 426, 427, 680, 682
Articles 406, 410, 411, 600, 605
Articles 545, 547, 550, 551, 552, 553, 555, 604, 675, Annex D, Examples D11 and D12
CMP-20 (Pre-2005 Code)
 
 

Home  | Join | Advertising | Seminars | Contact Us | Privacy Statement | Legal Notices
Copyright © 1997-2008 IAEI. All Rights Reserved.

Current Issue Home Page Issue Listing Series Focus on the Code Reprints Contacts Subscribe