Featured Images
Question 1
Enforcement of 440.65

Question 2
Minimum size devices on nameplates (breaker sizes)

Question 3
When 430.74 refers to the disconnecting means, does it mean the panel disconnect, the controller disconnect required in 430.102(A), or either?

Question 4
Is an additional disconnect needed for control power if separate from the motor power source?
 
 
 
IAEI News>Focus on the Code >CMP-11
Focus on the Code Questions for CMP-11
The Focus on the Code column is intended to assist our readers and members in understanding the requirements of the National Electrical Code. Our Code consultants consists of IAEI representatives on the CMP-11 panels of the NEC and other selected experts. 


Question 1. Is there any information on manufacturers that are building to the requirements listed in 440.65? Is anyone enforcing it? — G.G.

Answer 1.  NEC 440.65 requires factory installed leakage current detection and interruption (LCDI) or arc-fault circuit-interrupter (AFCI) protection for single-phase, cord-and-plug connected room air conditioners. As of June 2002, there are no listed air conditioners that employ either protective technique.

The UL standard for room air conditioners is being revised to require LCDI or AFCI protection. The revised standard may be issued yet this year. A revised standard normally permits manufacturers to take up to one year to make the necessary revisions to their product.

The National Electric Code recognizes that code changes may initiate changes in electrical appliances and utilization equipment. The NEC acknowledges that this process may not be complete by the time the authority having jurisdiction (AHJ) has adopted the newest version of the Code. Section 90.4 gives AHJs the ability to approve air conditioners listed to the current standard and installed to the most recent previous edition of the Code. —Tom Garvey, CMP-11.

| Return to top |


Question 2. I am very confused on what inspectors of Riverside County, California, are asking for on A/C condensers (breakers size). For example, if the condenser plate reading has a minimum breaker size of 24 amps, and a maximum breaker size of 35 amps, and I install a 30-amp breaker size, am I in the wrong? Inspectors are telling me that I should go to the max on the breaker. Are they correct? I cannot find this section in the NEC 1999. — F. A.

Answer 2.  This is not a violation of the Code unless the nameplate of the unit specifies a minimum size fuse or circuit breaker greater than 30 amperes. Section 440.4(B) in the NEC 2002 applies to air-conditioning equipment that contains a hermetic refrigerant motor compressor and other equipment such as a fan motor. The Code does not require manufacturers to list minimum size overcurrent protective device sizes on the nameplate. The nameplate must only indicate the maximum rating of the fuse or circuit breaker.

If the manufacturer elects to specify a minimum size device on the nameplate, NEC 110.3(B) would require the installer to abide by the nameplate information. — Tom Garvey, CMP-11.

| Return to top |


Question 3. I have a question related to 430.74, which states, "Motor control circuits shall be arranged so that they will be disconnected from all sources of supply when the disconnecting means is in an open position."

This is an industrial installation in which we have starter panels feeding multiple pieces of equipment in a process from the panel. The system is controlled by a PLC. The main disconnect switch on the panel interrupts the 480 VAC to the panel but the 120 VAC to the PLC I/O cards comes from a different supply and is not interrupted by the main disconnect switch.

When 430.74 refers to the disconnecting means does it mean the panel disconnect, the controller disconnect required in 430.102(A), or either?

By motor control circuits does the NEC mean just the wires to the coil, or are the status contacts from the aux contact included?

Does the NEC require that the main disconnect for a panel disconnect all sources of supply inside that panel?

I also have some questions related to E-stop circuitry. This is not covered by the NEC. Do you have any recommendations on good sources of information? I have tried NFPA 79 and some European standards but I am not sure if these are "binding," other than as good engineering practices. I need to have definitive documentation to get the money to make changes. —M.K.

Answer 3. Your first question refers to the requirement for a disconnecting means for the motor control circuit. The requirement is found in 430.74 of the 2002 NEC. The main disconnect can serve as the disconnecting means for power and control circuits for all of your starter panels. An acceptable alternative is the disconnecting means for an individual starter panel. The former option is very common for industrial processing equipment. Since the motor controllers act together in a coordinated fashion, often Exception 2 to 430.102(A) is employed. This exception permits a single disconnecting means for coordinated controllers operating multiple parts of a single machine or process.

Your second question refers to the definition for a motor control circuit. You ask if status signals are part of the control circuit. Status signals are not part of the motor control circuit. I refer you to Panel 11’s action on proposal 11-49 of the 2005 NEC Report on Proposals. The panel rejected a revised definition that would have included status signals as a type of motor control circuit.

Your last question asks if the main disconnect must disconnect all sources of supply inside that panel. No, multiple disconnects are permitted to make up the disconnecting means. Please note that if a separate disconnect is used for the motor control circuit, the control circuit disconnect shall be immediately adjacent to the supply circuit disconnect. This requirement is found in the last sentence of 430.74(A). This requirement is similar to 5.5.3 of the 2002 NFPA 79. NFPA 79 is more stringent than the NEC in this respect. Section 5.3.5.4 indicated that where circuits are not disconnected by the supply disconnecting means additional safety provisions such as warning labels are required.

You also indicated that you were looking for advice on E-stop circuitry. I would ask that you contact your company’s safety officer or your local OSHA compliance officer. They may have a strong opinion on NFPA 79 being "binding" in your facility. —Tom Garvey, CMP-11

| Return to top |


Question 4. Section 430.102(A) states, “An individual disconnecting means shall be provided for each controller and shall disconnect the controller.” (The controller is a set of contacts controlled by a magnetic coil or similar device, disconnecting its control power or all potential available within the environment of the controller enclosure.) Does this mean an additional disconnect is needed for control power if separate from the motor power source? (see figures 1, 2, and 3).

If exceptions listed under 430.102(B) are prevalent, do they apply to 430.102(A)? — B.G.

Answer 4. Your question refers to the disconnecting means requirement of the motor control circuits, the controller and motor, using 430.102(A) as a reference. First, let us begin with NEC Figure 430.1 to discover the appropriate parts of Article 430 to reference. Part VI contains the “Motor Control Circuits” requirements, and Part IX, “Motor Disconnecting Means.” Part VI, Section 430.74(A) requires motor circuit conductors to be arranged so that they will be disconnected from all sources of supply when the disconnecting means is in the open position. The disconnecting means shall be permitted to consist of two or more separate devices, one of which disconnects the motor and the controller from the sources of power supply for the motor, and the others, the motor control circuits from the supply. Where separate devices are used, they shall be located immediately adjacent to each other. Three exceptions do not appear to apply to the information as given.

Second, Part IX, Section 430.102(A) requires an individual disconnecting means that disconnects the controller to be in sight from the controller location. Section 430.102(B) requires a disconnecting means that disconnects the motor to be located in sight from the motor. This disconnecting means could be the same disconnect as required in 430.102(A) for the controller only if it is in sight from both the controller and motor. The exception to 430.102(B) permits the required motor disconnecting means to be out of sight of the motor under two conditions: (a) where being in sight is impracticable or introduces additional or increased hazards to persons or property; or (b) in industrial installations, with written safety procedures, where conditions of maintenance and supervision ensure only qualified persons service the equipment. Therefore, review the figures from the drawing presented by the reader: figure 1 violates both 430.74 and 430.102; figure 2 violates 430.74; and figure 3 complies. This review is based on the given information and assumes conditions (a) and (b) of 430.102(B) exception are not applicable.

You also inquired if the exceptions listed under 430.102(B) are prevalent, do they apply to 430.102(A)? These exceptions apply only to the heading under which they are located— 430.102(B), Motor—and not to 430.102(A), Controllers. I hope this answers your concerns. As always, it is suggested that one consult with the local authority having jurisdiction. — Tom Moore, CMP-11
(March/April 2007)

Return to top


The views of the authors of Focus on the Code and the editor are provided solely as a public service. 

The views expressed are not the official position of NFPA, the NEC Correlating Committee or any of its panels, IAEI, IAEI News, or the author's emplo


yers. Nor are they intended to represent a formal or informal interpretation of the NEC

 

 

Get Focused!

Articles 90, 100, 110, Annex A, Annex G
Articles 210, 215, 220, Annex D, Examples 1-6
Articles 300, 590, 720, 725, 760, Chapter 9, Tables 11(a) and (b), Tables 12(a) and (b)
Articles 225, 230
Articles 200, 250, 280, 285
Articles 310, 400, 402, Chapter 9 Tables 5 through 9, Annex B
Articles 320, 322, 324, 326, 328, 330, 332, 334, 336, 338, 340, 382, 394, 396, 398
Articles 342, 344, 348, 350, 352, 353, 354, 356, 358, 360, 362, 366, 368, 370, 372, 374, 376, 378, 380, 384, 386, 388, 390, 392, Chapter 9 Tables 1-4, Annex C
Articles 312, 314, 404, 408, 450, 490
Articles 240, 780
Articles 409, 430, 440, 460, 470, Annex D, Example D8
Articles 610, 620, 625, 630, 640, 645, 647, 650, 660, 665, 668, 669, 670, 685, Annex D, Examples D9 through D10
CMP-13
Articles 445, 455, 480, 490, 690, 692, 695, 700, 701, 702, 705
Articles 500, 501, 502, 503, 504, 505, 506, 510, 511, 513, 514, 515, 516
Articles 517, 518, 520, 525, 530, 540
Articles 770, 800, 810, 820, 830
Articles 422, 424, 426, 427, 680, 682
Articles 406, 410, 411, 600, 605
Articles 545, 547, 550, 551, 552, 553, 555, 604, 675, Annex D, Examples D11 and D12
CMP-20 (Pre-2005 Code)
 
 

Home  | Join | Advertising | Seminars | Contact Us | Privacy Statement | Legal Notices
Copyright © 1997-2008 IAEI. All Rights Reserved.

Current Issue Home Page Issue Listing Series Focus on the Code Reprints Contacts Subscribe